Division 7 - Thermal and Moisture Protection

Division 7 - Thermal and Moisture Protection
7.01 Firestopping



PART A - GENERAL

1.1  One Sub-contractor shall be responsible for the furnishing and
     installation of all building firestopping. This includes, but
     is not limited to, the following:

     A.   Through-penetration firestopping in fire-rated
          construction.

     B.   Construction-gap firestopping at connections of the same
          or different materials in fire rated construction.

     C.   Construction-gap firestopping occurring within fire rated
          wall, floor or floor-ceiling assemblies.

     D.   Construction-gap firestopping occurring at the top of
          fire rated walls.

     E.   Through-penetration smoke-stopping in smoke partitions.

     F.   Construction-gap smoke-stopping in smoke partitions.

1.2  The latest editions to the following publications shall apply
     as a minimum but not be all inclusive to the design and
     installation of firestopping. 

     A.   Underwriters Laboratories (UL)

          1.   UL Fire Resistance Directory (ULFRD)

          2.   Surface Burning Characteristics of Building
               Materials (UL 723)

          3.   Fire Tests of Through-Penetration Firestops (UL
               1479).

     B.   American Society For Testing And Materials Standards:
          ASTM E-814: Standard Test Method For Fire Tests of
          Through-Penetration Firestops.

     C.   Factory Mutual Engineering and Research Corporation (FM),
          Approval Guide.


     D.   National Fire Protection Association (NFPA). 

          1.   NFPA 101 -- Life Safety Code

          2.   NFPA 70 -- National Electric Code

          3.   NFPA 1 National Fire Prevention Code

     E.   Maryland State Fire Prevention Code (COMAR 12.03.01 and
          12.03.02)

     F.   Building Officials and Code Administrators International,
          INC. (BOCA).

          1.   BOCA National Building Code

          
Part B -  PRODUCTS

2.1  THROUGH-PENETRATION FIRESTOPPING OF FIRE-RATED CONSTRUCTION

     A.   Systems or devices listed in the U.L. Fire Resistance
          Directory under categories XHCR and XHEZ may be used,
          providing that it conforms to the construction type,
          penetrant type, annular space requirements, and fire
          rating involved in each separate instance, and that the
          system be symmetrical for wall applications. Systems or
          devices must be asbestos-free.

     B.   Only systems listed in the U.L. Fire Resistance directory
          for the U.L. System involved are acceptable.

     C.   All firestopping products must be from a single
          manufacturer.


2.2 CONSTRUCTION-GAP FIRESTOPPING OF FIRE-RATED CONSTRUCTION

     A.   Firestopping at construction gaps between edges of floor
          slabs and exterior wall construction.

     B.   Firestopping at construction gaps between tops of
          partitions and underside of structural systems.
     
     C.   Firestopping at construction gaps between tops of
          partitions and underside of ceiling or ceiling assembly.

     D.   Firestopping of control joints in fire-rated masonry
          partitions.

     E.   Firestopping expansion joints.

     F.   Acceptable manufacturers and products - those listed in
          the U.L. Fire Resistance Directory for the U.L. System
          involved.

2.3  SMOKE-STOPPING AT SMOKE PARTITIONS

     A.   Through-penetration smoke-stopping: Any system complying
          with the requirements for through-penetration
          firestopping in fire-rated construction provided that the
          system includes the specified smoke seal or will provide
          a smoke seal. The length of time of the fire resistance
          may be disregarded.

     B.   Construction-gap smoke-stopping: Any system complying
          with the requirements for construction-gap firestopping
          in fire-rated construction, is acceptable, provided that
          the system includes the specified smoke seal or will
          provide a smoke seal. The length of time of the fire
          resistance may be disregarded.

Part C -  INSTALLATION

     A.   Install penetration seal materials in accordance with
          printed instructions of the U.L. Fire Resistance
          Directory and in accordance with manufacturer's
          instruction.

     B.   Place firestopping in annular space around fire dampers
          before installation of damper's anchoring flanges which
          are installed in accordance with fire damper
          manufacturers recommendations.

     C.   Insulated Pipes and Ducts: Cut and remove thermal
          insulation where pipes or ducts pass through firestopping
          material. Replace thermal insulation with a material of
          equal thermal insulating characteristics and equal
          firestopping characteristics.

7.02 Joint Sealants


     All joint sealant materials shall be of the highest quality
     and shall meet the qualifications for the intended use.

7.03 Roofs and Moisture Control


     Tailoring of this guide specification is required to fit the
     type of roof designated to meet the specific design
     conditions.  Additional data and specific guidance for a
     project shall be obtained from the various manufacturers
     specified.  One copy of the contractor's submittal will be
     forwarded to Facilities Management through the Department of
     Architecture, Engineering, and Construction.

     A.   General

          1.   Specify copper or stainless steel flashing.

          2.   Specify sloped metal caps on parapet walls. Coping
               shall be minimum 20 oz. copper or 32 gage factory
               finish aluminum, installed with continuous cleats. 
               Each roof shall be covered by a 20 year, no dollar
               limit, manufacturer's renewable guarantee covering
               the complete roofing system including flashing. 
               Longer warranties may be appropriate depending upon
               the type of roof specified and accepted by FM.

          3.   Roof top equipment shall be raised a minimum of 18"
               from top of finished roof to bottom of unit for
               access during roof replacement.

          4.   Provide minimum 30# live load for roofs.

          5.   Metal Coping

               a.   Specify a slope of one (1) inch slope per foot
                    (to the roof side) on the top of coping.

               b.   If parapet wall is to be covered by a metal
                    coping, specify a continuous treated wood
                    blocking, covered by a layer of building paper
                    and metal coping to be cleated on both sides.

          6.   Gravel Stop and Counter-Cap Flashing

               a.   Specify copper or lead coated copper, all
                    seams and miters to be soldered.

               b.   Face of metal flashing to be cleated 30 inches
                    on center.

          7.   Roof Drains, Through-Wall Scuppers and Overflow
               Drainage Systems


               a.   Specify all roof drains and through - wall
                    scuppers (not overflow scuppers) to be sloped
                    2 ft. on center using taper insulation or
                    taper edge strip for positive drainage. 
                    However, through-wall scuppers are not
                    encouraged.

               b.   Install a copper gravel stop 1 inch x 4 inches
                    and 36 inches square minimum, set in flashing
                    cement around roof drains on built-up
                    aggregate roofing systems.  Apply a reflective
                    aluminum coating from gravel stop to drain
                    clamping ring.

               c.   All through wall scuppers shall empty into a
                    conductor head and downspout.

               d.   All overflow scuppers shall be set high enough
                    above the finished roof to ensured that water
                    doesn't drain through the overflow with a
                    normal rainfall.

     B.   Built-up Roofing Specifications

          1.   Substrate

               a.   Provide a minimum roof slope of 1/4" to 1/2"
                    per foot using light weight fill or taper
                    insulation toward drainage system (gutters,
                    roof drains, or through wall scuppers).

               b.   Slope built-up roof 6' square with taper
                    insulation toward roof drain and install
                    gravel stop 3' square minimum.

               c.   Specify conventional standard 4 ply fiberglass
                    felt built-up roof system with an aggregate
                    finished surface using #7 stone conforming to
                    ASTM # A - 4/7, minimum.

               d.   Provide walk out access to all roof levels for
                    maintenance personnel by use of penthouse
                    stairs or scuttle trap doors and stairway. 
                    Access ladders from one level to another are
                    required.
          2.   Insulation

               a.   The thickness shall be such that the
                    insulation's only value is equivalent to a
                    minimum of a R-18 value.  This value is for
                    the insulation only, not the complete roofing
                    system value.

               b.   All insulation shall be installed conforming
                    to U.L./F.M class 1/90 approval guide.

          3.   Base Flashing

               a.   All base flashing, shall be a minimum of 8
                    inches high from the finished roof surface.

               b.   Mechanically fasten top of base flashing, and
                    seal the top of all base flashing with
                    approved roofing cement and fabric before
                    applying metal counter flashing or metal cap
                    flashing.

          4.   Finished Surface

               a.   Clean gravel or slag (embed in bitumen flood
                    coat) meeting ASTM D 1863, which applies to
                    aggregates specified for use in bituminous
                    roofing.

               b.   White mineral surfaced cap sheet over ply
                    sheets of the built-up roofing system.

          5.   Guarantee

               a.   The contractor shall provide the University
                    with a written standard roofer's guarantee,
                    applicable to any leaks or failures due to
                    defective materials or workmanship, occurring
                    in the roof system or flashing within two
                    years from date of completion of the roof
                    work.  This does not include any limiting
                    penal sum.

               b.   The material's manufacturer shall provide the
                    University with a 20 year unlimited labor and
                    material guarantee similar to that offered by
                    Schuller in its "Signature Series, No Dollar
                    Limit, (NDL) Watertite Roofing System".

          6.   Access

               a.   Provide access to all roof levels by means of
                    penthouse doors, access ladders, or roof
                    hatch.

     C.   Slate Roofing System

          1.   Slate shall be 1/4 inch thick Buckingham, Vermont,
               Evergreen or equal and shall conform to physical
               requirements of grade S1 classifications.

          2.   Winter/Guard or equal shall be installed on hips,
               ridges, rakes, roof penetrations, eaves, and low
               pitched roof slopes (between 2/12 and 4/12).

          3.   Install snow guards on all "A" frame substrate
               roofing systems to protect entrances and gutters.

          4.   Guarantee

               A written guarantee shall be furnished that states
               the materials used are in strict accordance with
               the specifications, and that any and all repairs
               required on the roof due to defective materials or
               workmanship furnished under the contract shall be
               made without cost to the owner for a period of five
               years.

     D.   Shingle Roofing System

          1.   Shingle shall be 25 year class A fiber glass
               composition.

          2.   Winter/Guard or equal shall be installed on hips,
               ridges, rakes, roof penetrations, eaves, and low
               pitched roof slopes (2/12 and 4/12).

          3.   Install snow guards on all "A" frame substrate
               roofing systems to protect entrances and gutters.

          4.   The contractor shall provide the University with a
               written standard roofer's guarantee, applicable to
               any leaks or failures due to defective materials or
               workmanship, occurring in the roof system or
               flashing within two years from date of completion
               of the roof work. This does not include any
               limiting penal sum.

          5.   The material's manufacturer shall provide the
               University with a 25 year unlimited labor and
               material guarantee for a Watertite Roofing System.