Division 13 - Special Construction

Division 13 - Special Construction
13.01 Fire Alarm Systems


PART 1 - GENERAL

1.1  REQUIREMENTS -- The latest editions to the following codes and
     standards shall apply as a minimum but not be all inclusive to
     the design and installation of fire alarm systems: 

     A.   Maryland State Fire Prevention Code (COMAR 12.03.01 and
          12.03.02)

     B.   National Fire Protection Association (NFPA) 101 - Life
          Safety Code

     C.   Building Officials and Code Administrators International,
          INC. (BOCA) National Building Code

     D.   NFPA 1 National Fire Prevention Code

     E.   NFPA 70 - National Electrical Code

     F.   NFPA 72 - National Fire Alarm Code

     G.   NFPA 80 - Fire Doors and Windows

     H.   NFPA 90A - Standard for Air Conditioning and Ventilating
          Systems

     I.   NFPA 101 - Life Safety Code

     J.   NFPA 170 - Fire Safety Symbols     

     K.   ANSI/ASME A17.1 -- Safety Code For Elevators and
          Escalators as adopted by the State of Maryland.

     L.   Americans with Disabilities Act (ADA)        

1.2  SYSTEM DESCRIPTION

     A.   All new fire alarm and detection systems shall be
          analog/addressable systems.  

     B.   The system and components shall be the product of a
          single manufacturer.

1.3  QUALITY ASSURANCE -- The system and all components shall be
     listed by Underwriters Laboratory (UL) for fire protective
     signaling service (local and remote station, emergency
     communication and relocation equipment, and protective
     signaling systems) under UL 864.  

1.4  SEQUENCE OF OPERATION

     A.   Manual Pull Station:  Activation of any manual pull
          station shall automatically operate all audible and
          visual appliances and produce an alarm signal at the
          control unit and the remote annunciators. All manual pull
          station signals shall be automatically transmitted to
          UMCP Department of Facilities Management (FM) Work Control
          via CCMS as an "Alarm" signal. 

     B.   Smoke Detector: Activation of any smoke detector shall
          start the alarm verification mode. When the smoke
          detector latches into the alarm mode the fire alarm
          system shall automatically operate all audible and visual
          appliances and produce an alarm signal at the control
          unit and at the remote annunciators. All smoke detector
          alarm signals shall be automatically transmitted to 
          UMCP/FM Work Control via CCMS as an "Alarm" signal.

          1.   Elevator Recall - Smoke detectors at elevator
               landings, in elevator machine rooms, and in
               elevator shafts shall also recall the elevator(s)
               to the designated floor or to the designated
               alternate floor as required by the elevator safety
               code. 

          2.   Door release - Smoke detectors used to shut smoke
               or fire doors shall release the detector's
               associated door. Smoke detectors used to shut a
               door in a fire-rated stair enclosure shall release
               all of the doors in the stair enclosure. Each smoke
               detector used for door release shall be provided
               with an alarm verification feature and shall
               indicate a supervisory signal only.  

          3.   Suppression System Activation - Smoke detectors
               used to activate a fire suppression system (Pre-
               action sprinkler system, deluge system, or special
               extinguishing system) shall be crossed-zoned.
               Cross-zoning of detectors reduces the allowable
               spacing for the smoke detectors by «.  
     
     C.   Heat Detector: Activation of any heat detector shall
          automatically operate all audible and visual appliances
          and produce an alarm signal at the control unit and at
          the remote annunciators. All heat detector alarm signals
          shall be automatically transmitted to UMCP/FM Work
          Control via CCMS as an "Alarm" signal.  

          1.   Elevator Shunt-trip - Heat detectors in elevator
               shafts, and in elevator machine rooms shall also
               operate the shunt trip circuit breaker for the
               elevator main line in accordance with the elevator
               safety code. 

          2.   Suppression System Activation - Heat detectors may
               be used in conjunction with smoke detectors to
               activate a fire suppression system (Pre-action
               sprinkler system, deluge system, or special
               extinguishing system).

     D.   Water Flow Alarms:  Activation of a water flow alarm
          shall automatically operate all audible and visual
          appliances and produce an alarm signal at the control
          unit and at the remote annunciators. Each individual
          water flow switch shall have a distinct address. All
          water flow alarm signals shall be automatically
          transmitted to UMCP/FM Work Control via CCMS as a "Water
          Flow" signal.

     E.   Valve Tamper Switch:  Activation of a valve tamper switch
          shall initiate a supervisory alarm at the system control
          panel and at the remote annunciators. Supervisory audible
          and visible alarms at these locations shall be distinct
          from either alarm or trouble conditions involving the
          same or related devices. Each individual tamper switch
          shall have a distinct address. All valve tamper alarms
          shall be transmitted to UMCP/FM Work Control via CCMS as
          a "Valve Tamper" signal.

     F.   Duct Smoke Detector:  Activation of a duct smoke detector
          shall initiate a supervisory alarm at the system control
          panel and at the remote annunciators. A duct smoke
          detector activation shall also initiate an air handling
          unit shutdown as required by NFPA 90A. All duct detector
          alarms shall be transmitted to UMCP/FM Work Control via
          CCMS as a "Trouble" signal.

     G.   Fire Pump Supervisory Signals:  In buildings with fire
          pumps, individual supervisory signals shall be provided
          for the following conditions:  

          1.   Fire pump running

          2.   Fire pump loss of power in any phase

          3.   Fire pump phase reversal

          Activation of a fire pump supervisory signal shall
          initiate a supervisory alarm at the system control panel
          and at the remote annunciators. Each set of contacts in
          the fire pump controller shall have a distinct address.
          All fire pump supervisory signals shall be transmitted to
          UMCP/FM Work Control via CCMS as a "Trouble" signal.

     H.   High/low air pressure signals:  Buildings with dry-pipe
          or pre-action sprinkler systems shall provide a
          supervisory signal for system high and low air pressure. 
          Activation of a high/low air signal shall initiate a
          supervisory alarm at the system control panel and at the
          remote annunciators. Each pressure switch shall have a
          distinct address. All high/low air supervisory signals
          shall be transmitted to UMCP/FM Work Control via CCMS as
          a "Trouble" signal.

     I.   Trouble Signals:  Loss of primary power, short circuit,
          open faults, ground faults, missing detectors, abnormal
          detector status (e.g.:  dirty detector, replacement
          incompatible with the defined address), disabled devices
          and abnormal control functions shall initiate audible and
          visible trouble signals at the control unit and remote
          annunciators. Audible trouble signals shall sound until
          silenced. Silenced trouble signals shall be continuously
          indicated by a textual message and a trouble LED until
          restored to normal operation. The trouble LED shall
          remain illuminated until all abnormal conditions are
          cleared. Upon a return to normal operation, the audible
          trouble signal shall resound until restored to normal
          position. Subsequent trouble events shall resound audible
          trouble signals until silenced. All trouble events shall
          automatically be transmitted to UMCP/FM Work Control via
          CCMS as a "Trouble" signal.
     
     J.   Smoke Control Systems:

          1.   Stair Pressurization System -- Stair pressurization
               systems shall be activated for any alarm signal in
               the building. Stair pressurization systems shall
               also be manually activated at the annunciator panel
               with a key operated switch.

          2.   Atrium Smoke Removal Systems -- Atrium smoke
               removal systems shall be activated by any atrium
               waterflow switch or atrium smoke detector. Atrium
               smoke removal systems may also be manually
               activated at the atrium smoke removal control panel
               with a key operated switch.  

     K.   Special Door Locking Arrangements:

          1.   Delayed Egress Locks -- Doors with delayed egress
               locks installed in accordance with NFPA 101 shall
               unlock upon actuation of the fire alarm system.

          2.   Stair Enclosure Doors -- Stair doors that do not
               permit re-entry in accordance with NFPA 101 shall
               unlock upon actuation of the fire alarm system.


PART 2 - COMPONENTS

2.1  CONTROL PANEL

     A.   The fire alarm and detection system shall be 
          microprocessor based, power-limited, supervised, 24 VDC,
          non-coded system. The system shall be capable of
          providing the following functions:

          1.   Integral clock/calendar

          2.   Alarm verification (assigned by detector address)

          3.   Three-pulse temporal pattern evacuation signal

          4.   Functional walk-test of all initiating and
               signaling devices.

          The following manufacturers and systems, shall be
          acceptable:

          1.   Cerberus Pyrotronics - Model MXL 

          2.   Simplex Time Recorder - Model 4100 or 4120

          3.   Notifier - Model AM2020

     2.2  Fire Alarm Annunciator:  Textual annunciation shall be
          provided at the control unit and remotely in a location
          as approved by UMCP/DAEC. The textual display shall
          consist of an 80 character supertwist alphanumeric
          display, which shall include a 32 character user defined
          message for each device or function. All events displayed
          on the textual display shall also be recorded on an
          integral, 40-column, thermal strip printer.The connection
          between the remote annunciator and the system control
          panel shall be electrically supervised. A building
          graphic shall be provided above each remote annunciator. 
          Each building graphic shall include the building outline,
          all stairs, all exterior doors, all elevators, the
          location of the fire department connection, the location
          of the fire alarm control panel, the location of the main
          sprinkler valve, a North arrow, a "You Are Here"
          indicator, and the four sides of the building (Side 1,
          Side 2, Side 3, & Side 4) as indicated by UMCP/DAEC.

     2.3  Supervision:  Style 4 (Class B) supervision of all
          initiation devices is required. Notification appliance
          wiring shall also be Style Y (Class B).

     2.4  Power Supply:  Primary power shall consist of a two-wire
          120 VAC branch circuit from the emergency power
          distribution panel. The branch circuit disconnect shall
          be arranged and protected to prevent inadvertent
          disconnection and ensure optimum reliability. Standby
          power consisting of rechargeable batteries shall be
          provided. Batteries shall be capable of powering the
          system in the normal (standby) mode for 24 hours followed
          by 5 minutes of operation in the alarm mode (15 minutes
          for a voice system).
     
     2.5  Passwords and Security:  Access to control unit and
          remote annunciator switches wiring and power supplies
          shall be restricted by keyed-alike locks. Passwords shall
          be the same as the assigned University Building Number.

     2.6  VOICE/ALARM SYSTEMS

     A.   Each voice/alarm system shall be capable of providing the
          following functions: 

          1.   User defined automatic voice evacuation message.
               Message shall be in a fmelae voice.

          2.   Public address at control unit and at remote
               location(s) as required by UMCP/DAEC.

     B.   Public Address:  During some events and emergencies it
          may be desirable to disable the voice alarm system and
          direct occupants over the fire alarm speakers. In the
          public address mode, the voice alarm signals will be used
          to transmit instructions. The public address function
          shall be capable of manually overriding all other signals
          and users. A hand-held push-to-talk microphone shall be
          provided at the control panel and each remote panel.
          Microphone shall be supervised from disconnection. An
          audio control switch module shall be furnished to
          provided manual control of audio functions. These
          switches and associated LED indicators shall be
          supervised from disarrangement or failure. Audio power
          amplifiers shall be furnished with self-contained
          filtered 24VDC power supply, transformer, and amplifier
          monitor circuits. Amplifiers shall provided an output
          with a frequency response of 120 Hz to 12000 Hz. A
          sufficient quantity of amplifier capacity to operate all
          system speakers simultaneously plus 20 percent spare
          capacity shall be provided.

2.6  ALARM INITIATING DEVICES  

     Alarm initiating devices consist of conventional and analog
     detectors and manual stations connected to the system control
     unit via Style D or Style 6 (Class A) circuits.

2.7  Duct Smoke Detector Assemblies:  Duct smoke detector
     assemblies shall consist of an analog duct detector
     (ionization or photoelectric) and an air duct sampling
     assembly with sampling tube and detector housing. Each duct
     smoke detector shall be provided with a remote alarm lamp and
     keyed test switch located in a visible and accessible
     location.

2.8  Addressable Manual Station:  Manual stations shall be red in
     color, non-coded, double-action, nonbreak-glass type mounted
     in a semi-flush backbox. Manual station covers shall be hinged
     and secured with a lockset. Lockset shall be keyed the same as
     the control unit lockset. Manual pull stations installed in
     areas subject to damage, vandalism, and/or false alarms shall
     be protected by a STI Stopper II as manufactured by Safety
     Technology International, Inc.

2.9  Addressable Heat Detectors: Addressable heat detectors shall
     be plug-in type with base. The detector base shall be of the
     twist lock type with screw terminals for field wiring. Heat
     detectors shall be of the rate compensated type.

2.10 NOTIFICATION APPLIANCES  

     Alarm notification appliances shall consist of audible and
     visual signals for public signaling of fire. All notification
     appliances subject to damage and/or vandalism shall be
     protected by an STI Fire Alarm Signal Damage Stopper as
     manufactured by Safety Technology International, Inc.


PART 3 - EXECUTION

3.1  QUALIFICATIONS

     System design and installation shall be supervised by an
     experienced fire alarm technician or fire protection engineer
     with not less than five years experience with fire alarm
     systems. Shop drawings shall be prepared and signed by a class
     III Sprinkler Contractor licensed in the State of Maryland or a
     registered fire protection engineer. The signature of the
     technician or engineer constitutes an affidavit that the
     statements, representations, and information presented in the
     submittal constitute a complete operational system conforming
     with applicable state codes and recognized engineering
     practices. All field installation work shall be continuously
     supervised by a NICET Level II or III fire alarm system
     technician.  



3.2  FIRE ALARM CONTROL PANEL (FACP)

     A.   LOCATION:  The FACP shall be located in:

          1.   Buildings with automatic sprinkler system: In the
               same room as the sprinkler system alarm check
               valve.

          2.   Buildings without sprinkler system: In the main
               electrical room.

     B.   LOCKSET:  The lockset for the FACP shall be keyed for a
          "B" key, CAT15, or a "T45" key.

     C.   BATTERY BOX:  Auxiliary batteries shall be stored in a
          battery box located adjacent to the FACP. The lockset for
          the battery box shall be keyed the same as the FACP. 

3.3  ANNUNCIATOR PANEL

     Annunciator panels shall be located at the main entrance to
     the building, in a public area such as a lobby, and in plain
     view unobstructed by the opening of doors or other parts of
     the building. The lockset to gain access to the annunciator
     panel shall be keyed the same as for the FACP. Annunciator
     panels with reset functions that are not keyed activated shall
     be provided in a tamper proof locked cover to prevent
     unauthorized tampering.  

3.4  INITIATING DEVICES

     A.   Manual Pull Stations:  Manual pull stations shall be
          provided at the following locations:

          1.   At the exit from each floor at the stair enclosure
               exits on the corridor or room side located not more
               than 5 feet from the stair door.

          2.   At each door opening to the exterior of the
               building.

          3.   At the exit from each High-Hazard Occupancy (High-
               Hazard as defined by NFPA 101).

          4.   Manual pull stations shall be located so that the
               travel distance to any station from any point in
               the building does not exceed 200 feet.

          5.   At each exit from an Assembly Occupancy (Assembly
               Occupancy as defined by NFPA 101).

          6.   Telephone and electrical rooms in high-rise
               buildings.

          7.   Where required by NFPA 72.

          Manual pull stations shall be installed 42 to 54 in.
          above the finished floor. All manual pull stations shall
          be located to be readily accessible, unobstructed, and
          visible.

     B.   Smoke Detectors:  Analog smoke detectors shall be
          installed in accordance with NFPA 72 at the following
          locations:

          1.   At each elevator lobby as required by the elevator
               safety code.

          2.   In each elevator machine room as required by the
               elevator safety code.

          3.   At the top of each sprinklered elevator shaft and
               bottom of each sprinklered elevator shaft as
               required by the elevator safety code.

          4.   At un-enclosed vertical openings as required by
               NFPA 101.

          5.   At atriums for smoke removal systems as required by
               NFPA 101.

          6.   High-value and high-risk areas such as art
               galleries, archival records storage, musical
               instrument storage rooms, library stack areas, and
               computer rooms. 

          7.   At doors with magnetic hold-open devices.

          8.   For activation of a pre-action sprinkler system and
               other special fire suppression systems.

          9.   In all fire pump rooms.

          10.  At each FACP.

          All smoke detectors shall be programmed for a 30 second
          alarm verification cycle.

     C.   Duct Smoke Detectors:  Duct smoke detectors shall be
          provided for mechanical unit shutdown as required by NFPA
          90A.  

     D.   Heat Detectors:  Heat detectors shall be provided in
          accordance with NFPA 72 at the following locations:

          1.   In all sprinklered elevator machine rooms within
               two feet of the sprinkler head as required by the
               elevator safety code.

          2.   At the top of each sprinklered elevator shaft and
               bottom of each sprinklered elevator shaft within
               two feet of the sprinkler head as required by the
               elevator safety code.

          3.   In any unsprinklered storage room, mechanical room
               and electrical room.

          4.   As required for activation of a pre-action
               sprinkler system and other special fire
               extinguishing systems. 
     
     E.   Interface Modules (Monitor):  Addressable interface
          modules shall be provided to monitor any conventional
          (non-addressable) alarm notification appliance. Such as:

          1.   Non-addressable heat detectors.

          2.   Non-addressable smoke detectors.

          3.   Valve tamper switches, and sprinkler system
               butterfly valves.

          4.   Water flow switches.
     
          5.   Pressure switches.

          6.   Fire pump supervisory alarms.

          7.   Kitchen Suppression System Activation.

     F.   Interface Modules (Control):  Addressable interface
          modules shall be provided within three feet of the device
          being controlled for the control of the following
          auxiliary functions:

          1.   HVAC Shutdown: of respective air handler upon
               activation of associated duct smoke detector.

          2.   Door Holders: release doors automatically upon
               activation of associated smoke detector.

          3.   Door Lock Release: unlock all doors with special
               locking arrangements as required by NFPA 101.

          4.   Elevator recall: recall elevators as required by
               the elevator safety code.

          5.   Elevator Shunt Trip: operate the shunt trip circuit
               breaker for the elevator main line in accordance
               with the requirements of the elevator safety code.

     G.   Water Flow Detectors:  Water flow detectors shall be
          provided to monitor sprinkler systems for waterflow. 
          Water flow detectors shall be provided for the following:

          1.   At each alarm check valve (Pressure switch).

          2.   At each dry-pipe valve (Pressure switch).

          3.   At each pre-action system valve (Pressure switch).

          4.   At each sprinkler or standpipe system riser.

          5.   One flow switch per sprinkler system zone on each
               floor.  

          See the UMCP design guidelines for sprinkler and
          standpipe system for more specific information on water
          flow detectors.

     H.   Sprinkler/Standpipe Valves:  Provide supervision for each
          sprinkler/standpipe system control valve.
     
     I.   Fire Pump Supervision:  For each fire pump provide
          individual supervision of the following fire pump alarms:

          1.   Fire pump running.

          2.   Fire pump loss of power in any phase.

          3.   Fire pump phase reversal.

     J.   High/Low Air Pressure Supervision:  Provide supervision
          of low and high air pressure for each dry-pipe system and
          each pre-action system.

3.5  OFF-SITE SUPERVISION  

     Provide in or adjacent to the control panel, all equipment and
     wiring necessary to connect to system to the campus CCMS.
     Activation of any of the following signals shall automatically
     be reported to CCMS via relays:

     A.   Fire Alarm System in Alarm.  

     B.   Valve Tamper. 

     C.   System Trouble. 

     D.   Waterflow.

     E.   Fire Alarm System Power Off.

3.6  SPARE PARTS

     The fire alarm system contractor shall supply the University
     with a minimum of one replacement for each six devices (or
     fraction thereof) installed of the following devices:

     A.   Analog Smoke Detectors.

     B.   Addressable Manual Stations.

     C.   Interface Modules (monitor).

     D.   Interface Modules (control).

     E.   Horn/Strobe Signals. 
     
     F.   Speaker/Strobe Signals.

     G.   Strobe Signals.

     H.   Duct Smoke Detectors.

     I.   Door Hold Open Devices.

     J.   Addressable Heat Detectors.

3.7  SIGNS

     Provide and install 5 inch by 7 inch engraved red plastic
     signs with white lettering (helvetica or sans serif type)  
     above each manual pull station. Secure signs to surface with
     pan head screws and suitable anchors. These signs shall read
     as follows:

          IN CASE OF FIRE EMERGENCY!

          1.   PULL FIRE ALARM
          2.   LEAVE BUILDING
          3.   CALL FIRE DEPARTMENT
               DIAL 9-1-1

          The fire alarm is NOT connected to the fire department.

          Notify 405-2222 immediately if fire alarm system is
          disabled. 

3.8  WIRING
 
     All field wiring shall be installed in conduit. Conduit and
     boxes shall be sized according to National Electrical
     Code(R)requirements based on the number of conductors.
     Initiating device circuit wiring shall be two-conductor,
     twisted with integral shield and ground. Notification
     appliance circuits shall be minimum 14 AWG. Primary power (AC)
     branch circuit conductors shall be minimum 12 AWG. All
     conductors which are terminated, spliced, or otherwise
     interrupted shall be connected to terminal blocks. Make all
     connections with pressure type terminal blocks, which are
     securely mounted. The use of wire nuts or similar devices
     shall be prohibited.
     
     A.   Identification:  Fire alarm circuits shall be identified
          by red junction box covers stenciled in white letters
          "FIRE ALARM."

3.9  SYSTEM TESTING

     All initiating and notification appliances, control equipment,
     accessories, and auxiliary functions shall be tested in
     accordance with NFPA 72 acceptance test procedures.  

3.10 TRAINING

     Provide complete certified factory technical training for a
     minimum of two of the University's select representatives. 
     The University's select representatives shall, upon completion
     of the above training, be factory qualified to perform
     complete maintenance and repair of the fire alarm system. The
     contractor shall assume the responsibility to coordinate with
     the University the location and time required for the above
     certified factory technical training.

13.02 Fire-Suppression & Protection Systems


A.   CODE REQUIREMENTS

     All requirements of State of Maryland and the Office of the
     State Fire Marshal shall apply to the specifications and
     design requirements, including the following:

     A.   NFPA 1 National Fire Prevention Code

     B.   Underwriters Laboratories Inc. (UL), Fire Protection
          equipment list

     C.   Factory Mutual Approval Guide

     D.   Maryland Occupational Safety and Health Act

     E.   NFPA 13 - Standard for the Installation of Sprinkler
          Systems

     F.   NFPA 13D - Standard for the Installation of Sprinkler
          Systems in One- and Two-Family Dwellings and manufactured
          Homes

     G.   NFPA 13R - Standard for the Installation of Sprinkler
          Systems in Residential occupancies up to and Including
          Four Stories in Height

     H.   NFPA 14 - Standard for the Installation of Standpipe and
          Hose Systems

     I.   NFPA 15 - Standard for the Installation of Water Spray
          Fixed Systems

     J.   NFPA 20 - Standard for the Installation of Centrifugal
          Fire Pumps

     K.   NFPA 70 - National Electrical Code

     L.   NFPA 72 - National Fire Alarm Code

     M.   NFPA 101 - Life Safety Code

     N.   NFPA 170 - Fire Safety Symbols

     0.   NFPA 231 - General Storage

     P.   NFPA 231C - Rack Storage of Materials

     Q.   NFPA 1963 - Fire Hose Connections

     R.   UMCP Design Criteria Facilities Standards Manual for
          Architecture and Engineering Services (DCFS)

     S.   Washington Suburban Sanitary Commission (WSSC) - Plumbing
          and Gas Fitting Regulations

B.   PIPING

     A.   Connection shall be made to the UMCP on-site water
          system. The connection between -system piping and
          underground piping shall be made with a cast iron flanged
          piece, properly fastened.

     B.   A backflow preventer shall be installed in accordance
          with WSSC regulations. The backflow preventer shall be
          listed by UL for fire protection use.

     C.   All piping exposed installed outside, or otherwise
          exposed to weather, shall be externally galvanized.

C.   VALVES

     A.   All valves on connections to water supply to sprinklers
          shall be UL listed butterfly type indicating valves
          except for the following which shall be O.S.& Y:

          1.   All indicating valves on the supply side of the
               backflow preventer.

          2.   The indicating valve immediately adjacent to the
               backflow preventer on the system side.

          3.   All indicating valves on the suction side of the
               fire pump.

          4.   Where indicated on the contract drawings.
     
     B.   Post Indicator Valve - when indicated on the contract
          drawings, a gate valve on incoming water service shall be
          operable by a UL listed post indicator valve with tamper
          switch. Post indicator valve shall be installed a minimum
          of 40 feet from the building. 

D.   PIPING ACCESSORIES

     A.   No sprinkler piping is to be supported from any
          mechanical or electrical devices and/or equipment (ducts,
          lights,etc.). No,chains, wire or perforated band iron
          will be permitted for hangers. Hanger assemblies
          installed outside, or otherwise exposed to weather, shall
          be externally galvanized.

     B.   Install iron pipe sleeves of ample diameter at all points
          where pipes cut beams or floors or walls, so sized and
          installed that sprinkler pipes will not bend.

          1.   Install sleeve before walls or concrete work is
               built or poured, with sleeves being flush with wall
               surfaces.

          2.   Sleeves for underground pipes shall be caulked with
               oakum and molten lead and be watertight.

E.   SPRINKLERS

     A.   Sprinklers that may be subject to mechanical damage due
          to their location (under stairwells, low hanging
          sprinklers in corridors, storage rooms, under ducts,
          etc.) shall be provided with guards listed by UL for the
          model and type of sprinkler used.

     B.   Sprinklers under open grating shall be provided with
          approved shields.

F.   FIRE DEPARTMENT CONNECTIONS

     Each fire department connection shall be the flush type. Free
     standing type fire department connections shall only be
     installed when approved by UMCP/DAEC and shall be located a
     minimum of 40 feet from the building. Each fire department
     connection shall have two (two) 2-1/2 inch inlets with threads
     conforming to the American National Fire Hose Connection Screw
     Thread as defined in NFPA 1963, equipped with UL listed screw
     caps with pin lugs and chains.  The Fire department
     connections shall be not less than two feet and not more than
     3 feet 6 inches in elevation, measured from the ground level
     to the center line of the inlets. Two fire department
     connections are required when two or more risers are provided.

G.   DRAINS AND TEST PIPING

     A.   All risers, including the alarm check valve, shall be
          equipped with drains with sizes as specified in NFPA 13. 
          The alarm checkvalve drain ("main drain") shall be piped
          to the outside of the building at a point free from
          causing water damage. Where this arrangement is not
          practical, the   drain shall be piped to a floor drain or
          sump approved for the purpose by the Departments of
          Facilites Management and the UMCP/DES.

     B.   All drains and test piping shall piped to the outside of
          the building at a point free from causing water damage.
          Where this arrangement is not practical, the drain shall
          be piped to a f loor drain or sump approved for the
          purpose by the Departments of Facilities Management and the
          UMCP/DAEC.

H.   DRY PIPE SYSTEM

     Dry systems shall only be installed when adequate heat or
     insulation can not be provided to prevent sprinkler piping
     from freezing.

     A.   An air compressor (Reliable Model A or equivalent) with
          an automatic air maintenance device (Reliable Model B-1
          or equivalent) shall be, installed and sized in
          accordance with NFPA 13.

     B.   A separate test connection shall be provided in
          accordance with NFPA 13 to test the dry-pipe system
          alarms.
     
J.   PRE-ACTION SYSTEM

     Pre-action systems shall only be installed where required by
     UMCP/DAEC and the facility program.

     A.   The pre-action valve shall be activated by rate
          compensated heat detectors or cross-zoned smoke detection
          as approved UMCP/DAEC. Refer to section 13.1.

K.   FIRE PUMP, MOTOR AND CONTROLLER

     A fire pump shall only be installed when the existing water
     supply is not adequate to meet the required sprinkler demand.

L.   EXCESS PRESSURE PUMP
     
     An excess pressure pump shall be installed on all systems that
     do not have a fire pump. The excess pressure pump shall be
     Gamewell or equal 1/4 HP motor 120v single phase, 60 HZ.

M.   DRY STANDPIPE SYSTEM

     A.   Dry standpipe systems shall be the manual - -dry type as
          defined by NFPA 14.

     B.   Each standpipe riser shall be installed with a UL listed
          2« inch NST fire department hose valves with screw caps
          on each floor in an accessible, protected, and readily
          visible location in accordance with NFPA 14.

     C.   Each dry standpipe riser shall have a drain sized and
          located in accordance with NFPA 14. Each drain shall be
          piped outside the building in accordance with item 2.10.B
          of this section.

     D.   All dry piping shall be installed so that the entire
          system may be drained. The number of auxiliary drains
          shall be kept to a minimum.

     E.   All dry piping, hangers and fittings shall be galvanized.

     F.   Each dry standpipe shall be provided with an air and
          vacuum valve installed at the top of each riser. The air
          and vacuum valve shall be a 1 inch APCO Series 140 air
          and vacuum. valve, manufactured by Valve and Primer
          Corporation or approved equal.

N.   PROTECION

     Protection: All exposed piping devices (non-brass and chrome)
     are to be painted with two coats of bright red paint. Painting
     to conform to the protective coating section of the
     specifications.

O.   QUALIFICATIONS

     System design and installation shall be supervised by an
     experienced sprinkler system technician or fire protection
     engineer with not less than five years experience with
     sprinkler systems alarm systems. Shop drawings shall be
     prepared and signed by a Class III Sprinkler Contractor
     licensed in the State of Maryland or a registered fire
     protection engineer.  the signature of the technician or
     engineer constitutes an affidavit that the statements,
     representations, and information presented int he submittal
     constitute a complete operational system conforming with
     applicable state codes and recognized engineering practices.
     All field installation work shall be performed by a Class III
     Sprinkler Contractor licensed in the State of Maryland.

13.03 Fuel Storage Tanks


     A.   All installations/or removals must be in accordance with
          the requirements of OSHA, Federal, and State EPA
          regulations, COMAR, and The Maryland Department of the
          Environment and the International Mechanical Code.  Also
          Reference Section 1, Environmental Health and Safety in
          facility design for UST regulatory considerations/citation.
          The contractor shall be responsible for all required
          inspections and permit applications.

     B.   When at all possible, natural gas service or above ground
          fuel tanks are preferred over underground storage tanks.

     C.   Tanks shall be constructed of double wall fiberglass
          reinforced plastic (FRP) for underground use and double
          wall steel for above ground tanks.

     D.   Piping shall be either FRP or copper depending on size.

     E.   Material used in construction of the tank shall be
          compatible with the substance to be stored.

     F.   Low level alarm signal to DDC or Hawkeye as appropriate,
          and a high level alarm on a local horn or bell mounted at
          or near the tank vent approximately 8 foot above grade.

     G.   If the fuel storage tank is not located in the mechanical
          room with the generator set, then a remote level gauge
          near the generator is required.

     H.   Manholes, over-fill level alarms and/or other over-fill
          protection nozzles shall be provided as required.

     I.   Abandoned tanks must be removed and disposed of by the
          Contractor.

13.04 Wet Chemical Fire Extinguishing Systems


PART 1 - GENERAL

1.1  The installation of new wet chemical fire extingushing systems
     shall comply with the following:
     
     A.   FACTORY MUTUAL ENGINEERING AND RESEARCH CORPORATION (FM)
          Approval Guide

     B.   NFPA 17A -- Wet Chemical Extinguishing Systems

     C.   NFPA 70 -- National Electrical Code

     D.   NFPA 72 -- National Fire Alarm Code

     E.   NFPA 96 -- Ventilation Control and Fire Protection of
          Commercial Cooking Operations

     F.   UNDERWRITERS LABORATORIES INC. (UL)  Fire Protection
          Equipment Directory

     G.   UL 300 -- Fire Testing of Fire Extinguishing System for
          Protection of Restaurant Cooking Areas.

1.2  Qualifications      

     Installation drawings, shop drawings, and as-built drawings
     shall be prepared, by or under the supervision of, an
     individual who is experienced with the types of works
     specified herein, and is currently certified by the National
     Institute for Certification in Engineering Technologies 
     (NICET) as an engineering technician with minimum Level-III
     certification in Special Hazard System program.  Contractor
     shall submit data for approval showing the name and
     certification of all involved individuals with such
     qualifications at or prior to submittal of drawings.

PART 2 - PRODUCTS

2.1  PRE-ENGINEERED WET CHEMICAL FIRE EXTINGUISHING SYSTEMS
     
     Systems shall comply with NFPA 17A and NFPA 96, except as
     modified herein. Piping and accessories within the hoodshall
     be stainless steel or chrome plated.  All other piping shall
     be galvanized malleable iron or galvanized steel, painted to
     match the adjacent surface chrome or nickel plated or
     stainless steel or black steel painted to match the adjacent
     surface.  Exhaust hoods with grease extractors UL listed or FM
     approved are not required to have protection downstream of the
     grease extractors. Provide systems for protection of new or
     existing cooking equipment, including exhaust hoods and ducts
     for cooking equipment requiring protection by NFPA 96.

2.2  SYSTEM CONTROLS

     Each system shall be mechanically actuated by fusible links
     and by remote manual actuation stations connected to the
     extinguishing system release mechanisms by stainless steel
     cables.  Arrange each system to automatically shut off the
     flow of fuel and electrical power to cooking appliances as
     indicated [and to automatically actuate the building fire
     alarm fire alarm system as indicated. Electrical power to hood
     exhaust fans shall not be shut off unless specifically
     required by the UL listing or FM approval.

2.3  IDENTIFICATION SIGNS
  
     Provide red rigid plastic signs with engraved 6 mm (0.25 inch)
     high white lettering at each remote manual actuation station. 
     Sign legends shall be "Fire Extinguishing System" followed by
     a brief description of the equipment protected.

PART 3 - EXECUTION -- Tests and Inspection

     A representative of UMCP DAEC will witness formal tests and
     approve systems before acceptance.  Submit a written request
     for formal inspection at least 7 working days prior to
     inspection date.  An experienced technician regularly employed
     by the system installer shall be present during the
     inspection. At the inspection, repeat any or all of the
     required tests as directed. Provide plastic containers, hose
     fittings, and hose at each nozzle to capture the wet chemical
     and discharge each system to demonstrate uniform distribution
     of the wet chemical among the nozzles. Furnish compressed air,
     nitrogen, wet chemical equipment, and personnel for the tests.
     Refill and reset systems after tests have been completed.